TeSys D contactor
Published on : Tuesday 30-11--0001
Main
range |
TeSys
|
|
---|---|---|
product name |
TeSys D
|
|
product or component type |
Contactor
|
|
device short name |
LC1D
|
|
contactor application |
Motor control
Resistive load |
|
utilisation category |
AC-3
AC-1 AC-4 |
|
poles description |
3P
|
|
pole contact composition |
3 NO
|
|
[Ue] rated operational voltage |
<= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit |
|
[Ie] rated operational current |
25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
9 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit |
|
motor power kW |
2.2 kW at 400 V AC 50/60 Hz AC-4
2.2 kW at 220...230 V AC 50/60 Hz AC-3 4 kW at 380...400 V AC 50/60 Hz AC-3 5.5 kW at 500 V AC 50/60 Hz AC-3 5.5 kW at 660...690 V AC 50/60 Hz AC-3 4 kW at 415...440 V AC 50/60 Hz AC-3 |
|
motor power hp |
0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
|
control circuit type |
AC 50/60 Hz
|
|
[Uc] control circuit voltage |
230 V AC 50/60 Hz
|
|
auxiliary contact composition |
1 NO + 1 NC
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947
|
|
overvoltage category |
III
|
|
[Ith] conventional free air thermal current |
25 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit |
|
Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
|
rated breaking capacity |
250 A at 440 V for power circuit conforming to IEC 60947
|
|
[Icw] rated short-time withstand current |
105 A <= 40 °C 10 s power circuit
210 A <= 40 °C 1 s power circuit 30 A <= 40 °C 10 min power circuit 61 A <= 40 °C 1 min power circuit 100 A 1 s signalling circuit 120 A 500 ms signalling circuit 140 A 100 ms signalling circuit |
|
associated fuse rating |
20 A gG at <= 690 V coordination type 2 for power circuit
25 A gG at <= 690 V coordination type 1 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1 |
|
average impedance |
2.5 mOhm at 50 Hz - Ith 25 A for power circuit
|
|
[Ui] rated insulation voltage |
600 V for power circuit certifications CSA
600 V for power circuit certifications UL 690 V for power circuit conforming to IEC 60947-4-1 690 V for signalling circuit conforming to IEC 60947-1 600 V for signalling circuit certifications CSA 600 V for signalling circuit certifications UL |
|
electrical durability |
0.6 Mcycles 25 A AC-1 at Ue <= 440 V
2 Mcycles 9 A AC-3 at Ue <= 440 V |
|
power dissipation per pole |
0.2 W AC-3
1.56 W AC-1 |
|
protective cover |
With
|
|
mounting support |
Plate
Rail |
|
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
product certifications |
RINA
BV GOST DNV CSA UL LROS (Lloyds register of shipping) GL CCC |
|
connections - terminals |
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end |
|
tightening torque |
Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 |
|
operating time |
4...19 ms opening
12...22 ms closing |
|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
mechanical durability |
15 Mcycles
|
|
operating rate |
3600 cyc/h at <= 60 °C
|
Complementary
coil technology |
Without built-in suppressor module
|
|
---|---|---|
control circuit voltage limits |
0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
0.8...1.1 Uc operational at 60 °C, AC 50 Hz 0.85...1.1 Uc operational at 60 °C, AC 60 Hz |
|
inrush power in VA |
70 VA at 20 °C (cos ? 0.75) 60 Hz
70 VA at 20 °C (cos ? 0.75) 50 Hz |
|
hold-in power consumption in VA |
7.5 VA at 20 °C (cos ? 0.3) 60 Hz
7 VA at 20 °C (cos ? 0.3) 50 Hz |
|
heat dissipation |
2...3 W at 50/60 Hz
|
|
auxiliary contacts type |
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1 |
|
signalling circuit frequency |
25...400 Hz
|
|
minimum switching current |
5 mA for signalling circuit
|
|
minimum switching voltage |
17 V for signalling circuit
|
|
non-overlap time |
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact |
|
insulation resistance |
> 10 MOhm for signalling circuit
|
Environment
IP degree of protection |
IP20 front face conforming to IEC 60529
|
|
---|---|---|
protective treatment |
TH conforming to IEC 60068-2-30
|
|
pollution degree |
3
|
|
ambient air temperature for operation |
-5...60 °C
|
|
ambient air temperature for storage |
-60...80 °C
|
|
permissible ambient air temperature around the device |
-40...70 °C at Uc
|
|
operating altitude |
3000 m without derating in temperature
|
|
fire resistance |
850 °C conforming to IEC 60695-2-1
|
|
flame retardance |
V1 conforming to UL 94
|
|
mechanical robustness |
Vibrations contactor open 2 Gn, 5...300 Hz
Vibrations contactor closed 4 Gn, 5...300 Hz Shocks contactor open 10 Gn for 11 ms Shocks contactor closed 15 Gn for 11 ms |
|
height |
77 mm
|
|
width |
45 mm
|
|
depth |
86 mm
|
|
product weight |
0.32 kg
|
Offer Sustainability
Sustainable offer status |
Green Premium product
|
|
---|---|---|
RoHS (date code: YYWW) |
Compliant - since 0627 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity
|
|
REACh |
Reference not containing SVHC above the threshold
|
|
Product environmental profile |
Available Product environmental
|
|
Product end of life instructions |
Available End of life manual
|
Contractual warranty
Warranty period 18 months
It is used in Electrical industries.