Hybrid motor starter
Published on : Tuesday 30-11--0001
Short-circuit-proof hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 24 V DC input, 0.6 A output current, emergency stop function, and adjustable overload shutdown. Can only be used with EM-RD and EM-RI adapters or power distribution board.
Your advantages
- 22.5 mm wide
- Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
- Reduction in wiring
- Long service life
- Space saving
- Adjustable current for bimetal function
- Low-wear switching
Technical Specifications
Device supply
Rated control circuit supply voltage US |
24 V DC |
---|---|
Control supply voltage range |
19.2 V DC ... 30 V DC |
Rated control supply current IS |
40 mA |
Type of protection |
Surge protection |
|
Reverse polarity protection |
Input data
Input name |
Control input right/left |
---|---|
Rated actuating voltage UC |
24 V DC |
Triggering voltage range |
19.2 V DC ... 30 V DC |
Rated actuating current IC |
5 mA |
Switching threshold |
9.6 V (“0” signal) |
|
19.2 V (“1” signal) |
Switching level |
< 5 V DC (For EMERGENCY STOP) |
Typical turn-off time |
< 30 ms |
Type of protection |
Reverse polarity protection |
Output data load output
Output name |
AC output |
---|---|
Rated operating voltage Ue |
500 V AC |
Operating voltage range |
42 V AC ... 550 V AC |
Mains frequency |
50/60 Hz |
Load current range |
75 mA ... 600 mA (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 |
Class 10A |
Cooling time |
20 min. (for auto reset) |
Leakage current |
0 mA |
Type of protection |
Surge protection |
|
Short-circuit protection |
Output data reply output
Output name | Acknowledge output |
---|---|
Note | Confirmation: floating change-over contact, signal contact |
Contact type | 1 PDT |
Switching capacity according to IEC 60947-5-1 | 3 A (230 V, AC15) |
2 A (24 V, DC13) |
General
Switching frequency |
≤ 2 Hz (Load-dependent) |
---|---|
Mounting position |
vertical (horizontal DIN rail, motor output below) |
Mounting type |
DIN rail mounting |
Assembly instructions |
alignable, for spacing see derating |
Operating mode |
100% operating factor |
Maximum power dissipation |
2.8 W |
Minimum power dissipation |
0.88 W |
Operating voltage display |
Green LED |
Status display |
Yellow LED |
Indication |
Red LED |
Connection data, input side
Connection name |
Control circuits |
---|---|
Connection method |
Screw connection |
Stripping length |
8 mm |
Screw thread |
M3 |
Conductor cross section solid |
0.2 mm² ... 2.5 mm² |
Conductor cross section flexible |
0.2 mm² ... 2.5 mm² |
Conductor cross section AWG |
24 ... 14 |
Torque |
0.5 Nm ... 0.6 Nm |
Connection data, output side
Connection name |
Load circuit |
---|---|
Connection method |
Screw connection |
Stripping length |
8 mm |
Screw thread |
M3 |
Conductor cross section solid |
0.2 mm² ... 2.5 mm² |
Conductor cross section flexible |
0.2 mm² ... 2.5 mm² |
Conductor cross section AWG |
24 ... 14 |
Torque |
0.5 Nm ... 0.6 Nm |
Ambient conditions
Ambient temperature (operation) |
-25 °C ... 70 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) |
-40 °C ... 80 °C |
Degree of protection |
IP20 |
Dimensions
Width |
22.5 mm |
---|---|
Height |
160 mm |
Depth |
114.5 mm |
UL data
SCCR |
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
---|---|
|
5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) |
FLA |
0.6 A (480 V AC) |
Group installation |
20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded) |
|
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) |
Category code |
NLDX / NRNT |
Insulation characteristics
Rated insulation voltage |
500 V |
---|---|
Rated surge voltage |
6 kV |
Overvoltage category |
III |
Degree of pollution |
2 |
Designation |
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit |
Insulation |
Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC |
|
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC |
|
Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC |
|
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC |
Designation |
Isolation characteristics between the control input and control supply voltage to auxiliary circuit |
Insulation |
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
|
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Standards and Regulations
Designation |
Standards/regulations |
---|---|
Standards/regulations |
IEC 60947-1 |
|
EN 60947-4-2 |
|
IEC 61508 |
|
ISO 13849 |
ATEX |
? II (2) G [Ex e] [Ex d] [Ex px] |
|
? II (2) D [Ex t] [Ex p] |
Approvals/conformities
Safety Integrity Level according to IEC 61508 |
≤ 3 (Safe shutdown) |
---|---|
|
2 (Motor protection) |
Category acc. to EN ISO 13849 |
≤ 3 (Safe shutdown) |
Performance level according to ISO 13849 |
e (Safe shutdown) |
ATEX |
? II (2) G [Ex e] [Ex d] [Ex px] |
|
? II (2) D [Ex t] [Ex p] |
EU-type examination certificate |
PTB 07 ATEX 3145 |
UL certificate |
NLDX.E228652 |
Environmental Product Compliance
China RoHS |
Environmentally Friendly Use Period = 50 |
---|---|
|
|
It is used in Electrical Industries.
PHOENIX CONTACT (I) Pvt. Ltd.
Tel: 091670 07599