Multi-function Book type TOSVERT VF-MB1
Published on : Tuesday 30-11--0001
Capacity range
- 1 phase 240V-0.2~2.2kW
- 3 phase 500V-0.4~15kW
Features
1. Side-by-side installation
2.Slim design
3.Flat Mounting installation
4.Simple panel
5.Communication
6.Dual rating (CT/VT)
7.Induction motor and Permanent Magnetic (PM) motor drive
8.PM drive technology
1.Side-by-side installation
The VF-MB1 has been minimized width size in comparison with conventional model. In addition, side-by-side installation can save space in control cabinet.
2.Slim design
For 240V-0.2kW to 0.75kW and 500V-0.4kW to 1.5kW models are .. tted to 45mm slim design. And also, 240V-1.5kW to 2.2kW and 500V-2.2kW to 4.0kW models can be .. tted to 60mm.
3. Flat Mounting installation
The VF-MB1 can be mounted by Flat Mounting and front block can be attached 90 degree by using additional mount bracket (*2). The space can be minimized with various installation (*1).
*1: Current reduction is required if VF-MB1 is installed into less ventilation spaces such as narrow space and side-by-side installation.
*2: The model whose front block is attached 90 degree is modified with additional mount bracket in factory. Please request 90 degree type with order, if it is required.
4.Simple panel
Setting dial, 4 keys, and 4 small LEDs with Green 7 segments LEDs can be easy to set parameters and operations.
5.Communication
[Built-in (RJ45)]
- RS485 (Modbus® RTU) Baud rate 38.4 kbps max.
- CANopen®: Baud rate 1.0Mbps max.
[Optional (Add-on option)]
- EtherNet/IPTM-Modbus® TCP
- PROFIBUS® DP
- DeviceNetTM
- EtherCAT® (Coming soon)
- CANopen®: Baud rate 1.0Mbps max.
6.Dual rating (CT/VT)
The VF-MB1 can be used for the constant torque and variable torque applications by dual rating operation.
(5.5kW or larger type)
For example, if variable torque application (fan and pump) require 15kW drives, it can be operated by 11kW rated of VF-MB1.
7.Induction motor and Permanent Magnetic (PM) motor drive
The VF-MB1 controls not only 3-phase induction motors (Standard, High ef.. ciency motor) but also Interior Permanent Magnetic Motor (IPM) and Surface Permanent Magnetic Motor (SPM) for high ef.. ciency, high torque, energy saving, downsizing and lightening.
8.PM drive technology
Power-ON sensor less initial magnetic pole detection
Hit and stop function (Torque limit function)
Servo lock function
Sensor less step-out detection
Constant and Variable torque control
Technical Specifications
Item |
Specification |
|
Principal |
Control system |
Sinusoidal PWM control |
Output voltage range Note1) |
Adjustable within the range of 50 to 330V (240V class) and 50 to 660V (500V class) by correcting the supply voltage |
|
Output frequency range |
0.1 to 500.0Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 500Hz |
|
Minimum setting steps of frequency |
0.1Hz: analog input (when the max. frequency is 100Hz), 0.01Hz: Operation panel setting and communication setting. |
|
Frequency accuracy |
Digital setting: within +/-0.01% of the max. frequency (-10 to +60 degreeC) |
|
Voltage/frequency characteristics |
V/f constant, variable torque, automatic torque boost, vector control, automatic energy-saving. dynamic automatic energy-saving control, PM motor control, V/F 5-point setting, Auto-tuning. Base frequency (20-500Hz) adjusting to 1 & 2, torque boost (0-30%) adjusting to 1 & 2, adjusting frequency at start (0.1-10Hz) |
|
Frequency setting signal |
Setting dial on the front panel, external frequency potentiometer (connectable to a potentiometer with a rated impedance of 1k-10k ohm), 0-10Vdc / -10-+10Vdc (input impedance: 30k ohm), 4-20mAdc (Input impedance: 250 ohm). |
|
Terminal board base frequency |
The characteristic can be set arbitrarily by two-point setting. Possible to set: analog input (VIA, VIB, VIC). |
|
Frequency jump |
Three frequencies can be set. Setting of the jump frequency and the range. |
|
Upper- and lower-limit frequencies |
Upper-limit frequency: 0 to max. frequency, lower-limit frequency: 0 to upper-limit frequency |
|
PWM carrier frequency |
Adjustable range of 2.0k to 16.0kHz (default: 4.0kHz). |
|
PID control |
Setting of proportional gain, integral gain, differential gain and control wait time. Checking whether the amount of processing amount and the amount of feedback agree. |
|
Operation |
Acceleration/deceleration time |
Selectable from among acceleration/deceleration times 1 & 2 & 3 (0.0 to 3600 sec.). Automatic acceleration/deceleration function. S-pattern acceleration/ deceleration 1 & 2 and S-pattern adjustable. Control of forced rapid deceleration and dynamic rapid deceleration. |
DC braking |
Braking start-up frequency: 0 to maximum frequency, braking rate: 0 to 100%, braking time: 0 to 25.5 seconds, emergency DC braking, motor shaft fi xing control. |
|
Dynamic Braking Drive Circuit |
Control and drive circuit is built in the inverter with the braking resistor outside (optional). |
|
Input terminal function (programmable) |
Possible to select from among about 110 functions, such as forward/reverse run signal input, jog run signal input, operation base signal input and reset signal input, to assign to 8 input terminals. Logic selectable between sink and source. |
|
Output terminal functions (programmable) |
Possible to select from among about 150 functions, such as upper/lower limit frequency signal output, low speed detection signal output, specifi ed speed reach signal output and failure signal output, to assign to FL relay output, open collector output terminal, and RY output terminals. |
|
Forward/reverse run |
The RUN and STOP keys on the operation panel are used to start and stop operation, respectively. Forward/reverse run possible through communication and logic inputs from the terminal block. |
|
Jog run |
Jog mode, if selected, allows jog operation from the terminal board and also from remote keypad. |
|
Preset speed operation |
Base frequency + 15-speed operation possible by changing the combination of 4 contacts on the terminal board. |
|
Retry operation |
Capable of restarting automatically after a check of the main circuit elements in case the protective function is activated. 10 times (Max.) (selectable with a parameter) |
|
Various prohibition settings / Password setting |
Possible to write-protect parameters and to prohibit the change of panel frequency settings and the use of operation panel for operation, emergency stop or resetting. Possible to write-protect parameters by setting 4 digits password and terminal input. |
|
Regenerative power ride-through control |
Possible to keep the motor running using its regenerative energy in case of a momentary power failure (default: OFF). |
|
Auto-restart operation |
In the event of a momentary power failure, the inverter reads the rotational speed of the coasting motor and outputs a frequency appropriate to the rotational speed in order to restart the motor smoothly. This function can also be used when switching to commercial power. |
|
Light-load high-speed operation |
Increases the operating effi ciency of the machine by increasing the rotational speed of the motor when it is operated under light load. |
|
Drooping function |
When two or more inverters are used to operate a single load, this function prevents load from concentrating on one inverter due to unbalance. |
|
Override function |
External input signal adjustment is possible to the operation frequency command value. |
|
Relay output signal |
1c- contact output and 1a- contact output: Note2) |
|
Protective |
Protective function |
Stall prevention, current limitation, over-current, output short circuit, over-voltage, over-voltage limitation, undervoltage, ground fault, detection, input phase failure, output phase failure, overload protection by electronic thermal function, armature over-current at start-up, load side over-current at start-up, over-torque, undercurrent, overheating, cumulative operation time, life alarm, emergency stop, various pre-alarms |
Electronic thermal characteristic |
Switching between standard motor and constant-torque VF motor, switching between motors 1 & 2, setting of overload trip time, adjustment of stall prevention levels 1 & 2, selection of overload stall |
|
Reset function |
Function of resetting by closing contact 1a or by turning off power or the operation panel. This function is also used to save and clear trip records. |
|
Display |
Alarms |
Over-current, overvoltage, overload, overheat, communication error, under-voltage, setting error, retry in process, upper/lower limits |
Causes of failures |
Over-current, overvoltage, overheat, output short-circuit, ground fault, overload on inverter, arm overcurrent at start-up, overcurrent on the load side at start-up, CPU fault, EEPROM fault, RAM fault, ROM fault, communication error. (Selectable: dynamic braking resistor overload, emergency stop, under-voltage, small current, over-torque, motor overload, input phase failure, output phase failure) |
|
Monitoring function |
Operation frequency, operation frequency command, forward/reverse run, output current, input voltage (DC detection), output voltage, torque, load factor of inverter, input power, output power, information on input terminals, information on output terminals, version of CPU1, version of CPU2, PID feedback value, frequency command (after compensation), causes of past trips 1to 8, parts replacement alarm, cumulative operation time, overload and region setting |
|
Past trip monitoring function |
Stores data on the past eight trips: number of trips that occurred in succession, operation frequency, opreation frequency command, forward/reverse run, output current, input voltage (DC detection), output voltage, information on input terminals, information on output terminals, and cumulative operation time when each trip occurred. |
|
Output for frequency meter |
Analog output for meter: 1mA dc full-scale dc ammeter |
|
4-digit 7-segments LED |
Frequency: inverter output frequency. |
|
Indicator |
Lamps indicating the inverter status by lighting, such as RUN lamp, MON lamp, PRG lamp, % lamp, Hz lamp, EASY lamp, CANopen lamp, NET lamp. The charge lamp indicates that the main circuit capacitors are electrically charged. |
|
Environments |
Location of use |
Indoors; not exposed to direct sunlight, corrosive gas, explosive gas, fl ammable gas, oil mist, or dust; and vibration of less than 5.9m/s2 (10 to 55Hz). |
Elevation |
3000 m or less (current reduction required over 1000 m) Note 3) |
|
Ambient temperature |
-10 to +60 degreeC Note 4) |
|
Storage temperature |
-25 to +70 degreeC |
|
Relative humidity |
5 to 95% (free from condensation and vapor). |
It is used in Oil And Gas, Electrical, Chemical Industry