Pro-MEC VCB Vacuum Circuit Breakers
Published on : Tuesday 30-11--0001
General
-
High reliability of the operating mechanism
-
Separate design of the main circuit from the operating mechanism.
-
Adopt the toggle link method.
-
Improved the reliability of electric circuit.
-
Adopt the rapid auto-reclosing method as a standard option.
(O-0.3sec.-CO-3min.-CO)
-
-
High interrupting performance
-
Make short of the interrupting time. (3cycles)
-
Increase the rated short-circuit withstand characteristics. (1sec. to 3sec.)
-
Reinforce the insulation in the conduct, by adopting the molded housing in each phase.
-
Built in the device making the contacts open first when draw in and out.
-
Adopt the tulip-shape connection between the cradle and the VCB.
-
Great operational safety
Ratings
-
Rated voltage: 7.2kV, 12kV, 17.5kV, 24kV
-
Rated normal current: 630A, 1250A, 2000A, 2500A
-
Rated short-time withstand current: Max. 40kA
Wide range of accessories (optional)
Applied standard: IEC 62271-100 (M2, E2(List1), C2 class)
Certification: KEMA, KERI
High reliability of the operating mechanism
-
Separate design of the main circuit from the operating mechanism.
-
Adopt the toggle link method.
-
Improved the reliability of electric circuit.
-
Adopt the rapid auto-reclosing method as a standard option. (O-0.3sec.-CO-3min.-CO)
High interrupting performance
-
Make short of the interrupting time. (3cycles)
-
Increase the rated short-circuit withstand characteristics. (1sec. to 3sec.)
Great operational safety
-
Reinforce the insulation in the conduct, by adopting the molded housing in each phase.
-
Built in the device making the contacts open first when draw in and out.
-
Adopt the tulip-shape connection between the cradle and the VCB.
|
||||
---|---|---|---|---|
Type |
LVB-06=-20D |
LVB-06=-25D |
||
Rated voltage (kV) |
7.2 |
7.2 |
||
Rated normal current (A) |
630 1250 2000 |
630 1250 2000 |
||
Rated frequency (Hz) |
50/60 |
50/60 |
||
Rated short-circuit breaking current (kA) |
20 |
25 |
||
Rated short-circuit breaking capacity (MVA) |
250 |
310 |
||
Rated short-time withstand current (kA/3sec) |
20 |
25 |
||
Rated short-circuit making current (kAp) |
52 |
65 |
||
Rated breaking time (Cycle) |
3 |
3 |
||
Rated opening time (sec) |
≤ 0.04 |
≤ 0.04 |
||
No-load closing time (sec) |
≤ 0.06 |
≤ 0.06 |
||
Withstand |
Power frequency (kV/min) |
20 |
20 |
|
Impulse (kV/1.2×50?) |
60 |
60 |
||
Rated operating sequence |
O-0.3s-CO-3min-CO |
O-0.3s-CO-3min-CO |
||
Type test |
Electrical |
M2 (10,000 times) |
M2 (10,000 times) |
|
Mechanical |
E2 (List1) |
E2 (List1) |
||
Capacitive current switching Note 1) |
C2 |
C2 |
||
Lifetime |
Maintenance |
Without maintenance (Time) |
20000 |
20000 |
Maintenance (Time) |
30000 |
30000 |
||
Electrical |
Without maintenance (Time) |
20000 |
20000 |
|
Maintenance (Time) |
30000 |
30000 |
||
Auxiliary switch |
4a4b, 10a10b |
4a4b, 10a10b |
Type |
LVB-06=-32D |
LVB-06=-40D |
||
---|---|---|---|---|
Rated voltage (kV) |
7.2 |
7.2 |
||
Rated normal current (A) |
1250 2000 3150 |
1250 2000 3150 |
||
Rated frequency (Hz) |
50/60 |
50/60 |
||
Rated short-circuit breaking current (kA) |
31.5 |
40 |
||
Rated short-circuit breaking capacity (MVA) |
390 |
500 |
||
Rated short-time withstand current (kA/3sec) |
31.5 |
40 |
||
Rated short-circuit making current (kAp) |
82 |
104 |
||
Rated breaking time (Cycle) |
3 |
3 |
||
Rated opening time (sec) |
≤ 0.04 |
≤ 0.04 |
||
No-load closing time (sec) |
≤ 0.06 |
≤ 0.06 |
||
Withstand |
Power frequency (kV/min) |
20 |
20 |
|
|
|
|
|
|
|
|
|
|
|