Generator circuit-breaker HEC 9 for 250-300 kA
Published on : Tuesday 30-11--0001
The world’s largest generator circuit-breaker (GCB)
HEC 9 has been developed as a system for large sized power plant such as nuclear, coal fired and hydro power plants. It has the world's highest performance with short-circuit currents up to 300 kA and it is also highly suitable for retrofits or replacements of old GCBs in air-blast technology.
Based on ABB’s well proven and highly reliable SF6 technology, it enables lower lifecycle costs and gives a time-to-overhaul period of up to 20 years.
It is delivered in single-phase systems to facilitate the transportation and installation with plug-in design to minimize the activities at site. Besides circuit-breaker, disconnector, capacitors and control cubicle, it also includes a wide selection of additional components such as earthing and starting switches, current and voltage transformers, and surge arresters.
Applications
-
Load current up to 33,500 A
-
Power units up to 2000 MW
-
Indoor or outdoor installations
-
Replacements or retrofits of old units
Why ABB?
-
Naturally cooled up to 28,500 A
-
Delivers the highest performance rates
-
Provides the lowest lifecycle costs - maximum system availability and reliability
-
Based on SF6, it is the only alternative to old and obsolete GCBs in air-blast technology
-
Fully type tested according to IEEE C37.013, the worldwide GCB standard
Brief performance data
System Type
|
HEC 9-250L
|
HEC 9-250XL
|
HEC 9-300L
|
HEC 9-300XL
|
Rated maximum voltage [kV] |
31.5
|
31.5
|
31.5
|
31.5
|
Rated frequency [Hz] |
50 / 60
|
50 / 60
|
50 / 60
|
50 / 60
|
Rated power frequency withstand voltage [kV] |
80
|
80
|
80
|
80
|
Rated lightning impulse withstand voltage [kV] |
150
|
150
|
150
|
150
|
Rated short-circuit breaking current [kA] |
250
|
250
|
300
|
300
|
|
|
|
|
|
HEC 9 with 50 Hz *) |
|
|
|
|
Rated normal current [A]: natural cooled |
up to 28,500
(naturally cooled) |
up to 33,500
(enhanced convection) |
up to 28,500
(naturally cooled) |
up to 33,500
(enhanced convection) |
|
|
|
|
|
HEC 9 with 60 Hz *) |
|
|
|
|
Rated normal current [A]: natural cooled |
up to 26,500
(naturally cooled) |
up to 32,500
(enhanced convection) |
up to 26,500
(naturally cooled) |
up to 32,500
(enhanced convection) |
*) with IPB longitudinal forced air cooling |
up to 57,000
|
|
up to 57,000
|
|
ABB India Limited